• 1
  • 2
Product Range
 
Fan Coil
One Way Cassette Fan Coil Series
Views:3420   Updated:2014/7/4 19:08:52


STRUCTURE

Beautiful Panels and frame are made from high grade plastic, pressure injection and right assemble.

HEAT EXCHANGER

The coil is made of hydrophilic aluminum finned copper tube, optimum FPI increasing heat transfer efficiency .The connections have brass header with female fittings and equipped with air vent ,pipe into the drain pan.

FAN

Centrifugal fan and direct drive motor. Each fan is statically and dynamically balanced to ensure quiet operation and optimum performance..

DRAIN TRAY

Drain tray is treated with polyester powder painting anti corrosion and well insulation anti condensate .

FILTER

Easy removed filter is made of polypropylene fabric, which is washable type.

FILTER

Remote controller is standard and offered.

OPTIONAL

1.Balancing valve   2.Two or three way Valve   3.Wired controller

TECHNICAL DATA

Product Type

FCU-34Ca/1W

FCU-51Ca/1W

FCU-68Ca/1W

FCU-85Ca/1W

Air Flow

High

m3/h

340

510

680

850

Middle

m3/h

279

418

558

697

Low

m3/h

170

255

340

425

Total cooling capacity

High

W

2170

3120

4090

4920

Middle

W

1953

2819

3738

4350

Low

W

1579

2323

3010

3504

Total heating capacity

High

W

3497

5014

6738

7618

Middle

W

3044

4358

5652

6817

Low

W

2518

3710

4986

5637

Fan motor Input power

 

W

37

52

62

76

Power  Supply

 

V/PH/Hz

220/1/50/60

Controlling method

 

 

remote controller

Noise

 

dB(A)

37

38

39

40

Water Flow

kg/h

373

536

703

846

Water Resistence

kPa

10

10

20

20

water pipe connections

mm

ZG3/4"(DN20)

Draining pipe

mm

Rc3/4"(DN20)

Unit dimension (L×W×H)

net

mm

850×400×235

850×400×235

850×400×235

850×400×235

packaging

mm

990×435×290

990×435×290

990×435×290

990×435×290

Panel dimension (L×W×H)

net

mm

1050×470×18

1050×470×18

1050×470×18

1050×470×18

packaging

mm

1150×530×172

1150×530×172

1150×530×172

1150×530×172

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 27℃/WB 19.5℃ , water inlet/outlet temperature 7℃/ 12℃   

*Heating capacity is measured under the condition : Ambient temperature DB 21℃, water inlet temperature 60℃


<<<<<< Previous:Ducted Fan Coil Units - FP Series              Next:Wall Mounted Fan Coil Series >>>>>>
ALK Air Conditioning (c) Copyright 2020 Group Email